100
9.483
-5.69
0.0569
<
-5.375
0.055
Dh =-1.6
S h /q =0.2839
Dh =-1.5
S h /q =0.29
Dqк =-2.81
Dqк =-2.57
3
7—3
1200
300
57.8538
8.533
+10.24
0.1770
57.4138
8.412
+10.094
0.176
7—1
850
350
130.3882
7.42
-6.307
0.0484
128.0182
7.152
-6.08
0.047
1—2
690
250
36.4482
11.019
-7.603
0.2086
34.0782
9.719
-6.708
0.197
2—3
600
300
99.3308
9.357
-5.614
0.0565
96.9608
8.915
-5.349
0.055
Dh =-2.32
S h /q =0.4905
Dh =-2.01
S h /q =0.475
Dqк =-2.37
Dqк =-2.11
Друге наближення
^q, л/с
1000i, м / км
h = 1000і× l, м
h /q
233.77
6.482
+20.741
0.089
40.6524
4.43
+3.101
0.076
246.87
7.228
-21.685
0.088
Dh =0.719
S h /q =0.1729
Dqк =2.079
40.6524
4.43
-3.101
0.076
149.2841
9.726
+13.13
0.0879
52.632
7.151
-5.935
0.113
185.1804
7.506
-10.884
0.059
Dh =-1.69
S h /q =0.3359
Dqк =-2.52
185.1804
7.506
+10.884
0.059
56.9538
8.286
-9.944
0.175
94.62
8.49
-5.094
0.0538
Dh =-1.38
S h /q =0.2878
Dqк =-2.4
56.9538
8.286
+9.944
0.175
125.9082
6.919
-5.881
0.047
31.9682
8.628
-5.953
0.1862
94.8508
8.532
-5.119
0.054
Dh =-1.75
S h /q =0.4622
Dqк =-1.89
Третє наближення
^q, л/с
1000i, м / км
h = 1000і× l, м
h /q
231.691
6.367
+20.374
0.087
36.0534
3.552
+2.486
0.069
248.949
7.351
-22.052
0.087
Dh =0.26
S h /q =0.243
Dqк =0.535
36.0534
3.552
-2.486
0.069
151.804
10.057
+13.577
0.089
50.112
6.527
-5.417
0.108
185.0604
7.497
-10.87
0.058
Dh =-1.3
S h /q =0.324
Dqк =-2
185.0604
7.497
+10.87
0.058
56.4438
8.147
-9.778
0.173
92.22
8.065
-2.419
0.026
Dh =-0.44
S h /q =0.249
Dqк =-0.88
56.4438
8.147
+9.778
0.173
124.1082
6.713
-5.706
0.046
30.0782
7.705
-5.316
0.177
92.9608
8.037
-4.822
0.052
Dh =-1.5
S h /q =0.448
Dqк =-1.67
Четверте наближення
^q, л/с
1000i, м / км
h = 1000і× l, м
h /q
231.156
6.338
+20.28
0.087
33.5184
3.107
+2.175
0.065
249.484
7.382
-22.147
0.088
Dh =0.103
S h /q =0.24
Dqк =0.21
33.5184
3.107
-2.175
0.065
153.804
10.324
+13.937
0.09
48.112
6.051
-5.022
0.104
183.9404
7.406
-10.739
0.06
Dh =-0.99
S h /q =0.319
Dqк =-1.55
183.9404
7.406
+10.739
0.06
57.2338
8.363
-10.035
0.18
91.34
7.912
-2.072
0.023
Dh =-0.43
S h /q =0.263
Dqк =-0.8
57.2338
8.363
+10.035
0.18
122.4382
6.543
-5.561
0.045
28.4082
6.931
-4.782
0.17
91.2908
7.903
-4.742
0.05
Dh =-1.25
S h /q =0.445
Dqк =-1.5
П’яте наближення
^q, л/с
1000i, м / км
h = 1000і× l, м
h /q
230.946
6.326
+20.243
0.088
31.7584
2.815
+1.971
0.062
249.694
7.395
-22.184
0.0889
Dh =0.01
S h /q =0.2389
Dqк =0.002
31.7584
2.815
-1.971
0.062
155.354
10.533
+14.22
0.09
46.562
5.694
-4.726
0.1
183.1904
7.346
-10.652
0.058
Dh =-0.78
S h /q =0.31
Dqк =-1.25
183.1904
7.346
+10.652
0.058
57.9338
8.555
-10.266
0.17
90.54
7.774
-1.982
0.022
Dh =-0.532
S h /q =0.25
Dqк =-1.1
57.9338
8.555
+10.266
0.17
120.9382
6.383
-5.426
0.04
26.9082
6.269
-4.326
0.16
89.7908
7.646
-4.587
0.05
Dh =-1
S h /q =0.42
Dqк =-1.2
витрата
вода водопровідний мережа
Шосте наближення
^q, л/с
1000i, м / км
h = 1000і× l, м
h /q
230.944
6.327
+20.244
0.0876
30.5064
2.616
+1.931
0.0632
249.694
7.396
-22.184
0.0888
Dh =-0.003
S h /q =0.2388
Dqк =-0.00628
30.5064
2.616
-1.831
0.0632
156.604
10.703
+14.45
0.0922
45.312
5.414
-4.494
0.0991
183.0404
7.334
-10.634
0.058
Dh =-0.45
S h /q =0.3056
Dqк =-0.7362
183.0404
7.334
+10.634
0.058
58.0338
8.583
-10.299
0.177
89.44
7.586
-1.638
0.018
Dh =-0.43
S h /q =0.253
Dqк =-0.8498
58.0338
8.583
+10.299
0.177
118.7382
6.153
-5.23
0.044
24.7082
5.357
-3.696
0.14
87.5908
7.276
-4.365
0.049
Dh =-0.74
S h /q =0.41
Dqк =-1
Сьоме наближення
^q, л/с
1000i, м / км
h = 1000і× l, м
h /q
230.95
6.327
+20.244
0.0876
29.7824
2.616
+1.731
0.0623
249.698
7.396
-21.184
0.0872
Dh =0.004
S h /q =0.2371
Dqк =0.0016
29.7824
2.616
-1.631
0.0623
157.604
10.703
+14.46
0.0921
44.123
5.414
-4.194
0.0987
184.154
7.534
-10.826
0.0596
Dh =-0.25
S h /q =0.2942
Dqк =-0.354
184.154
7.534
+10.826
0.0596
58.184
8.583
-10.299
0.177
88.45
7.586
-1.456
0.018
Dh =-0.23
S h /q =0.176
Dqк =-0.4238
58.184
8.583
+10.299
0.177
117.7382
6.151
-5.1
0.044
23.6082
5.355
-3.243
0.14
86.4968
7.254
-4.12
0.049
Dh =-0.46
S h /q =0.26082
Dqк =-0.567
Восьме наближення
^q, л/с
1000i, м / км
h = 1000і× l, м
h /q
230.94
6.327
+20.244
0.0876
29.7812
2.616
+1.931
0.0632
249.699
7.396
-22.184
0.0888
Dh =-0.002
S h /q =0.2145
Dqк =-0.0012
29.7812
2.616
-1.631
0.0223
157.958
10.703
+14.46
0.0321
43.145
5.414
-4.194
0.0487
184.254
7.534
-10.826
0.0396
Dh =-0.15
S h /q =0.186
Dqк =-0.124
184.254
7.534
+10.826
0.0295
58.284
8.583
-10.299
0.0177
88.45
7.586
-1.456
0.018
Dh =-0.12
S h /q =0.02808
Dqк =-0.234
58.284
8.583
+10.299
0.0177
117.7382
6.151
-5.1
0.044
23.6082
5.355
-3.243
0.13
86.4968
7.254
-4.12
0.019
Dh =-0.28
S h /q =0.174
Dqк =-0.267
SDh=0.552
8. Вибір
матеріалу і діаметрів труб ділянок мережі
Для водопровідної
мережі у межах населеного пункту та для водоводів призначаємо чавунні труби.
По визначеним
попереднім розрахунковим витратам ділянок мережі при режимі максимального
водоспоживання намічаємо економічно вигідні діаметри головних магістральних
ліній, користуючись таблицями для гідравлічного розрахунку [2]. Перевіряємо можливість пропуску
витрати води по них в режимі пожежогасіння. Назначаємо діаметри перемичок на
сортамент меньше діаметра магістралей, що до них примикають.
9. Визначення витрат напору в
трубах та ув’язка кілець
Гідравлічний
розрахунок водопроводу виконуємо для всіх розрахункових режимів (табл.14-16).
Втрати напору на ділянках водопровідної мережі визначаємо за формулою:
h = S × q2, м,
де q – витрата води на ділянці, л/с; S – опір ділянки
Ув'язку кілець виконуємо
методом Шевелева. За програмою “таблиці
Шевелева”.
Гідравлічний розрахунок
трубопроводів на відгалуженнях для підключення підприємств виконуємо (табл.
17), використовуючи [2]. Передбачаємо прокладання
трубопроводів в одну нитку, вважаючи це допустимим за вимогами надійності
водозабезпечення даних виробництв.
Талиця 17
Гідравлічний
розрахунок трубопроводів для підключення підприємств
Ділянка
Довжина
Діаметр
Витрата
Швидкість
1000і
h=1000і*l
2
0,25
400
157
1,241
5.396
1,38
5
0,15
250
44.23
0.88
5.177
0,864
6
0,15
200
43.77
1.358
15.717
0,8385
10. Визначення
вільних напорів та п’єзометричних
відміток у вузлах водопровідної мережі
Вільні напори
визначаємо в усіх вузлах магістральної водопровідної мережі і водоводів на всі
розрахункові режими роботи водопроводу. Для цього креслимо розрахункові схеми
мережі, на яких вказуємо значення, отримані при гідравлічному розрахунку.
Потрібний вільний
напір Нтр визначаємо
залежно від поверховості будинків:
Нтр=
4(n – 1) + 10, м,
де
n – кількість поверхів.
Значення
фактичних вільних напорів у вузлах водопровідної мережі визначаємо за формулою
Нвіл.і = Пі
– Zз.і, м,
де
Пі – п'єзометрична
відмітка у і-му вузлі водопровідної мережі; Zз.і – відмітка поверхні землі у цій же
точці.
Значення Пі в
інших вузлах мережі визначаємо при послідовному обході всіх вузлових точок за
формулою:
Пі+1
= Пі ± hі, м,
в
якій величину втрати напору hі між двома точками мережі берємо із знаком «мінус», якщо напрям обходу
точок збігається з напрямом руху води на ділянці, а в іншому разі приймають
знак «плюс».
Диктуючою
точкою для режимів максимального і водоспоживання та пожежогасіння буде вузол 2.
Диктуючою
точкою для режиму транзиту буде вузол 6.
Для
режиму пожежогасіння вільні напори у всіх вузлах мережі повинні бути не меншими
10 м і не більшими 60 м.
На
основі виконаного гідравлічного розрахунку мережі та визначених вільних напорів
і п'єзометричних відміток складаємо розрахункові схеми для усіх розрахункових
режимів та будуємо профіль по зовнішньому контуру водопровідної мережі.
№ вузла
НС-ІІ
5
6
7
1
2
3
4
НС-ІІ
l, м
3200
1350
830
1000
690
1050
1200
3000
Zземлі, м
122
122.5
125.5
123.5
122.5
120.5
119.5
120.5
122
Пі.max, м
191.937
169.008
171.438
164.766
160.332
154.5
159.639
172.983
191.937
Пі.пож, м
181.993
159.961
149.958
143.905
136.9
130.5
136.438
157.673
181.993
Пі.транз , м
194.213
173.96
159.5
163.694
168.794
172.037
173.993
172.029
194.213
Птр.госп, м
144.5
159.5
157.5
156.5
154.5
153.5
142.5
Птр.пож, м
132.5
135.5
133.5
132.5
130.5
129.5
130.5
Список літератури
1.
СниП 2.04.02-84.
Водоснабжение. Наружные сети и сооружения. /Госстрой СССР. – М., Стройиздат,
1985. – 136 с.
2.
Шевелев Ф.А.,
Шевелев А.Ф. Таблицы для гидравлического расчета водопроводных труб. Справочное
пособие. М., Стройиздат, 1984. – 116 с.
3.
А.М.Тугай,
В.О.Орлов, В.О.Шадура, С.Ю.Мартинов. Міські інженерні мережі та споруди. Підручник. – Київ:
Укргеліотех, 2010. – 256с.
4.
Тугай
А.М., Терновцев В.О., Тугай Я.А. Розрахунок і проектування споруд систем
водопостачання: Навчальний посібник. – КНУБА, 2001. – 256с.
5.
Хоружий П.Д.,
Хомутецька Т.П., Хоружий В.П. Ресурсозберігаючі технології водопостачання. – К:
Аграрна наука, 2008 – 534 с.
6.
Хоружий
П.Д., Ткачук О.А. Водопровідні системи і споруди: Навч. посібник. – К.: Вища
шк., 1993. – 230 с.: іл.
Прізвище , група
Варіант
18
1.
Кількість населення:
I район
- 42000 осіб
II район - 28000 осіб
2.
Кількість поверхів забудови міста:
I район
- 7
II район - 4
3.
Ступінь благоустрою житлової забудови (СНиП 2.04.02-84, табл..1):
I район
- з централізованим гарячим водопостачанням
II район - без ванн
4.
Зона розташування міста
- середня
5.
Промислові
підприємства:
6.
Довжина напірних водоводів - 3,0 км та 3,2 км
7.
Відмітка поверхні землі біля насосної станції II підйому - 122,0 м
8.
Генплан міста (М 1:20000)
100 | 9.483 | -5.69 | 0.0569 | <-5.375 | 0.055 | ||||||
Dh =-1.6 | S h /q =0.2839 | Dh =-1.5 | S h /q =0.29 | ||||||||
Dqк =-2.81 |
Dqк =-2.57 |
||||||||||
3 | 7—3 | 1200 | 300 | 57.8538 | 8.533 | +10.24 | 0.1770 | 57.4138 | 8.412 | +10.094 | 0.176 |
7—1 | 850 | 350 | 130.3882 | 7.42 | -6.307 | 0.0484 | 128.0182 | 7.152 | -6.08 | 0.047 | |
1—2 | 690 | 250 | 36.4482 | 11.019 | -7.603 | 0.2086 | 34.0782 | 9.719 | -6.708 | 0.197 | |
2—3 | 600 | 300 | 99.3308 | 9.357 | -5.614 | 0.0565 | 96.9608 | 8.915 | -5.349 | 0.055 | |
Dh =-2.32 | S h /q =0.4905 | Dh =-2.01 | S h /q =0.475 | ||||||||
Dqк =-2.37 |
Dqк =-2.11 |
Друге наближення | |||
^q, л/с | 1000i, м / км |
h = 1000і× l, м |
h /q |
233.77 | 6.482 | +20.741 | 0.089 |
40.6524 | 4.43 | +3.101 | 0.076 |
246.87 | 7.228 | -21.685 | 0.088 |
Dh =0.719 | S h /q =0.1729 | ||
Dqк =2.079 |
|||
40.6524 | 4.43 | -3.101 | 0.076 |
149.2841 | 9.726 | +13.13 | 0.0879 |
52.632 | 7.151 | -5.935 | 0.113 |
185.1804 | 7.506 | -10.884 | 0.059 |
Dh =-1.69 | S h /q =0.3359 | ||
Dqк =-2.52 |
|||
185.1804 | 7.506 | +10.884 | 0.059 |
56.9538 | 8.286 | -9.944 | 0.175 |
94.62 | 8.49 | -5.094 | 0.0538 |
Dh =-1.38 | S h /q =0.2878 | ||
Dqк =-2.4 |
|||
56.9538 | 8.286 | +9.944 | 0.175 |
125.9082 | 6.919 | -5.881 | 0.047 |
31.9682 | 8.628 | -5.953 | 0.1862 |
94.8508 | 8.532 | -5.119 | 0.054 |
Dh =-1.75 | S h /q =0.4622 | ||
Dqк =-1.89 |
Третє наближення | |||
^q, л/с | 1000i, м / км |
h = 1000і× l, м |
h /q |
231.691 | 6.367 | +20.374 | 0.087 |
36.0534 | 3.552 | +2.486 | 0.069 |
248.949 | 7.351 | -22.052 | 0.087 |
Dh =0.26 | S h /q =0.243 | ||
Dqк =0.535 |
|||
36.0534 | 3.552 | -2.486 | 0.069 |
151.804 | 10.057 | +13.577 | 0.089 |
50.112 | 6.527 | -5.417 | 0.108 |
185.0604 | 7.497 | -10.87 | 0.058 |
Dh =-1.3 | S h /q =0.324 | ||
Dqк =-2 |
|||
185.0604 | 7.497 | +10.87 | 0.058 |
56.4438 | 8.147 | -9.778 | 0.173 |
92.22 | 8.065 | -2.419 | 0.026 |
Dh =-0.44 | S h /q =0.249 | ||
Dqк =-0.88 |
|||
56.4438 | 8.147 | +9.778 | 0.173 |
124.1082 | 6.713 | -5.706 | 0.046 |
30.0782 | 7.705 | -5.316 | 0.177 |
92.9608 | 8.037 | -4.822 | 0.052 |
Dh =-1.5 | S h /q =0.448 | ||
Dqк =-1.67 |
Четверте наближення | |||
^q, л/с | 1000i, м / км |
h = 1000і× l, м |
h /q |
231.156 | 6.338 | +20.28 | 0.087 |
33.5184 | 3.107 | +2.175 | 0.065 |
249.484 | 7.382 | -22.147 | 0.088 |
Dh =0.103 | S h /q =0.24 | ||
Dqк =0.21 |
|||
33.5184 | 3.107 | -2.175 | 0.065 |
153.804 | 10.324 | +13.937 | 0.09 |
48.112 | 6.051 | -5.022 | 0.104 |
183.9404 | 7.406 | -10.739 | 0.06 |
Dh =-0.99 | S h /q =0.319 | ||
Dqк =-1.55 |
|||
183.9404 | 7.406 | +10.739 | 0.06 |
57.2338 | 8.363 | -10.035 | 0.18 |
91.34 | 7.912 | -2.072 | 0.023 |
Dh =-0.43 | S h /q =0.263 | ||
Dqк =-0.8 |
|||
57.2338 | 8.363 | +10.035 | 0.18 |
122.4382 | 6.543 | -5.561 | 0.045 |
28.4082 | 6.931 | -4.782 | 0.17 |
91.2908 | 7.903 | -4.742 | 0.05 |
Dh =-1.25 | S h /q =0.445 | ||
Dqк =-1.5 |
П’яте наближення | |||
^q, л/с | 1000i, м / км |
h = 1000і× l, м |
h /q |
230.946 | 6.326 | +20.243 | 0.088 |
31.7584 | 2.815 | +1.971 | 0.062 |
249.694 | 7.395 | -22.184 | 0.0889 |
Dh =0.01 | S h /q =0.2389 | ||
Dqк =0.002 |
|||
31.7584 | 2.815 | -1.971 | 0.062 |
155.354 | 10.533 | +14.22 | 0.09 |
46.562 | 5.694 | -4.726 | 0.1 |
183.1904 | 7.346 | -10.652 | 0.058 |
Dh =-0.78 | S h /q =0.31 | ||
Dqк =-1.25 |
|||
183.1904 | 7.346 | +10.652 | 0.058 |
57.9338 | 8.555 | -10.266 | 0.17 |
90.54 | 7.774 | -1.982 | 0.022 |
Dh =-0.532 | S h /q =0.25 | ||
Dqк =-1.1 |
|||
57.9338 | 8.555 | +10.266 | 0.17 |
120.9382 | 6.383 | -5.426 | 0.04 |
26.9082 | 6.269 | -4.326 | 0.16 |
89.7908 | 7.646 | -4.587 | 0.05 |
Dh =-1 | S h /q =0.42 | ||
Dqк =-1.2 |
витрата вода водопровідний мережа
Шосте наближення | |||
^q, л/с | 1000i, м / км |
h = 1000і× l, м |
h /q |
230.944 | 6.327 | +20.244 | 0.0876 |
30.5064 | 2.616 | +1.931 | 0.0632 |
249.694 | 7.396 | -22.184 | 0.0888 |
Dh =-0.003 | S h /q =0.2388 | ||
Dqк =-0.00628 |
|||
30.5064 | 2.616 | -1.831 | 0.0632 |
156.604 | 10.703 | +14.45 | 0.0922 |
45.312 | 5.414 | -4.494 | 0.0991 |
183.0404 | 7.334 | -10.634 | 0.058 |
Dh =-0.45 | S h /q =0.3056 | ||
Dqк =-0.7362 |
|||
183.0404 | 7.334 | +10.634 | 0.058 |
58.0338 | 8.583 | -10.299 | 0.177 |
89.44 | 7.586 | -1.638 | 0.018 |
Dh =-0.43 | S h /q =0.253 | ||
Dqк =-0.8498 |
|||
58.0338 | 8.583 | +10.299 | 0.177 |
118.7382 | 6.153 | -5.23 | 0.044 |
24.7082 | 5.357 | -3.696 | 0.14 |
87.5908 | 7.276 | -4.365 | 0.049 |
Dh =-0.74 | S h /q =0.41 | ||
Dqк =-1 |
Сьоме наближення | |||
^q, л/с | 1000i, м / км |
h = 1000і× l, м |
h /q |
230.95 | 6.327 | +20.244 | 0.0876 |
29.7824 | 2.616 | +1.731 | 0.0623 |
249.698 | 7.396 | -21.184 | 0.0872 |
Dh =0.004 | S h /q =0.2371 | ||
Dqк =0.0016 |
|||
29.7824 | 2.616 | -1.631 | 0.0623 |
157.604 | 10.703 | +14.46 | 0.0921 |
44.123 | 5.414 | -4.194 | 0.0987 |
184.154 | 7.534 | -10.826 | 0.0596 |
Dh =-0.25 | S h /q =0.2942 | ||
Dqк =-0.354 |
|||
184.154 | 7.534 | +10.826 | 0.0596 |
58.184 | 8.583 | -10.299 | 0.177 |
88.45 | 7.586 | -1.456 | 0.018 |
Dh =-0.23 | S h /q =0.176 | ||
Dqк =-0.4238 |
|||
58.184 | 8.583 | +10.299 | 0.177 |
117.7382 | 6.151 | -5.1 | 0.044 |
23.6082 | 5.355 | -3.243 | 0.14 |
86.4968 | 7.254 | -4.12 | 0.049 |
Dh =-0.46 | S h /q =0.26082 | ||
Dqк =-0.567 |
Восьме наближення | |||
^q, л/с | 1000i, м / км |
h = 1000і× l, м |
h /q |
230.94 | 6.327 | +20.244 | 0.0876 |
29.7812 | 2.616 | +1.931 | 0.0632 |
249.699 | 7.396 | -22.184 | 0.0888 |
Dh =-0.002 | S h /q =0.2145 | ||
Dqк =-0.0012 |
|||
29.7812 | 2.616 | -1.631 | 0.0223 |
157.958 | 10.703 | +14.46 | 0.0321 |
43.145 | 5.414 | -4.194 | 0.0487 |
184.254 | 7.534 | -10.826 | 0.0396 |
Dh =-0.15 | S h /q =0.186 | ||
Dqк =-0.124 |
|||
184.254 | 7.534 | +10.826 | 0.0295 |
58.284 | 8.583 | -10.299 | 0.0177 |
88.45 | 7.586 | -1.456 | 0.018 |
Dh =-0.12 | S h /q =0.02808 | ||
Dqк =-0.234 |
|||
58.284 | 8.583 | +10.299 | 0.0177 |
117.7382 | 6.151 | -5.1 | 0.044 |
23.6082 | 5.355 | -3.243 | 0.13 |
86.4968 | 7.254 | -4.12 | 0.019 |
Dh =-0.28 | S h /q =0.174 | ||
Dqк =-0.267 |
|||
SDh=0.552 |
8. Вибір матеріалу і діаметрів труб ділянок мережі
Для водопровідної мережі у межах населеного пункту та для водоводів призначаємо чавунні труби.
По визначеним попереднім розрахунковим витратам ділянок мережі при режимі максимального водоспоживання намічаємо економічно вигідні діаметри головних магістральних ліній, користуючись таблицями для гідравлічного розрахунку [2]. Перевіряємо можливість пропуску витрати води по них в режимі пожежогасіння. Назначаємо діаметри перемичок на сортамент меньше діаметра магістралей, що до них примикають.
9. Визначення витрат напору в трубах та ув’язка кілець
Гідравлічний розрахунок водопроводу виконуємо для всіх розрахункових режимів (табл.14-16). Втрати напору на ділянках водопровідної мережі визначаємо за формулою:
h = S × q2, м,
де q – витрата води на ділянці, л/с; S – опір ділянки
Ув'язку кілець виконуємо методом Шевелева. За програмою “таблиці Шевелева”.
Гідравлічний розрахунок трубопроводів на відгалуженнях для підключення підприємств виконуємо (табл. 17), використовуючи [2]. Передбачаємо прокладання трубопроводів в одну нитку, вважаючи це допустимим за вимогами надійності водозабезпечення даних виробництв.
Талиця 17
Гідравлічний розрахунок трубопроводів для підключення підприємств
Ділянка | Довжина | Діаметр | Витрата | Швидкість | 1000і | h=1000і*l |
2 | 0,25 | 400 | 157 | 1,241 | 5.396 | 1,38 |
5 | 0,15 | 250 | 44.23 | 0.88 | 5.177 | 0,864 |
6 | 0,15 | 200 | 43.77 | 1.358 | 15.717 | 0,8385 |
10. Визначення вільних напорів та п’єзометричних відміток у вузлах водопровідної мережі
Вільні напори визначаємо в усіх вузлах магістральної водопровідної мережі і водоводів на всі розрахункові режими роботи водопроводу. Для цього креслимо розрахункові схеми мережі, на яких вказуємо значення, отримані при гідравлічному розрахунку.
Потрібний вільний напір Нтр визначаємо залежно від поверховості будинків:
Нтр= 4(n – 1) + 10, м,
де n – кількість поверхів.
Значення фактичних вільних напорів у вузлах водопровідної мережі визначаємо за формулою
Нвіл.і = Пі – Zз.і, м,
де Пі – п'єзометрична відмітка у і-му вузлі водопровідної мережі; Zз.і – відмітка поверхні землі у цій же точці.
Значення Пі в інших вузлах мережі визначаємо при послідовному обході всіх вузлових точок за формулою:
Пі+1 = Пі ± hі, м,
в якій величину втрати напору hі між двома точками мережі берємо із знаком «мінус», якщо напрям обходу точок збігається з напрямом руху води на ділянці, а в іншому разі приймають знак «плюс».
Диктуючою точкою для режимів максимального і водоспоживання та пожежогасіння буде вузол 2.
Диктуючою точкою для режиму транзиту буде вузол 6.
Для режиму пожежогасіння вільні напори у всіх вузлах мережі повинні бути не меншими 10 м і не більшими 60 м.
На основі виконаного гідравлічного розрахунку мережі та визначених вільних напорів і п'єзометричних відміток складаємо розрахункові схеми для усіх розрахункових режимів та будуємо профіль по зовнішньому контуру водопровідної мережі.
№ вузла | НС-ІІ | 5 | 6 | 7 | 1 | 2 | 3 | 4 | НС-ІІ |
l, м |
3200 | 1350 | 830 | 1000 | 690 | 1050 | 1200 | 3000 | |
Zземлі, м |
122 | 122.5 | 125.5 | 123.5 | 122.5 | 120.5 | 119.5 | 120.5 | 122 |
Пі.max, м |
191.937 | 169.008 | 171.438 | 164.766 | 160.332 | 154.5 | 159.639 | 172.983 | 191.937 |
Пі.пож, м |
181.993 | 159.961 | 149.958 | 143.905 | 136.9 | 130.5 | 136.438 | 157.673 | 181.993 |
Пі.транз , м |
194.213 | 173.96 | 159.5 | 163.694 | 168.794 | 172.037 | 173.993 | 172.029 | 194.213 |
Птр.госп, м |
144.5 | 159.5 | 157.5 | 156.5 | 154.5 | 153.5 | 142.5 | ||
Птр.пож, м |
132.5 | 135.5 | 133.5 | 132.5 | 130.5 | 129.5 | 130.5 |
Список літератури
1. СниП 2.04.02-84. Водоснабжение. Наружные сети и сооружения. /Госстрой СССР. – М., Стройиздат, 1985. – 136 с.
2. Шевелев Ф.А., Шевелев А.Ф. Таблицы для гидравлического расчета водопроводных труб. Справочное пособие. М., Стройиздат, 1984. – 116 с.
3. А.М.Тугай, В.О.Орлов, В.О.Шадура, С.Ю.Мартинов. Міські інженерні мережі та споруди. Підручник. – Київ: Укргеліотех, 2010. – 256с.
4. Тугай А.М., Терновцев В.О., Тугай Я.А. Розрахунок і проектування споруд систем водопостачання: Навчальний посібник. – КНУБА, 2001. – 256с.
5. Хоружий П.Д., Хомутецька Т.П., Хоружий В.П. Ресурсозберігаючі технології водопостачання. – К: Аграрна наука, 2008 – 534 с.
6. Хоружий П.Д., Ткачук О.А. Водопровідні системи і споруди: Навч. посібник. – К.: Вища шк., 1993. – 230 с.: іл.
Прізвище , група
Варіант 18
1. Кількість населення:
I район - 42000 осіб
II район - 28000 осіб
2. Кількість поверхів забудови міста:
I район - 7
II район - 4
3. Ступінь благоустрою житлової забудови (СНиП 2.04.02-84, табл..1):
I район - з централізованим гарячим водопостачанням
II район - без ванн
4. Зона розташування міста - середня
5. Промислові підприємства:
6. Довжина напірних водоводів - 3,0 км та 3,2 км
7. Відмітка поверхні землі біля насосної станції II підйому - 122,0 м
8. Генплан міста (М 1:20000)